电气火灾报警系统

网络释义

  SPN AXC

电气火灾报警系统SPN AXC),电气火灾报警系统SPN AXC)批发,消防...

基于24个网页-相关网页

有道翻译

电气火灾报警系统

Electrical fire alarm system

以上为机器翻译结果,长、整句建议使用 人工翻译

双语例句

  • 本文火灾原因分析引出火灾自动报警系统消防配电线路规范设计问题进行研究,希望电气线路引起火灾降低

    Started from the cause of the fire, the paper researched on the fire alarm system and fire regulate distribution line design problems in the hope to reduce fires caused by the electrical circuits.

    youdao

  • 摘要高大开放式空间建筑火灾自动报警系统设计现代建筑电气设计新兴难点领域

    The design of automatic fire alarm system for high and large open space buildings is the new and difficult areas for electrical design of modern building electricity design.

    youdao

  • 通过电气火灾产生机理说明设置漏电火灾报警系统预防电气火灾重要性

    This paper explains the importance of installing current leakage fire alarm system in the protection of electricity fire disaster through analysis of the developing mechanism of electricity fire.

    youdao

更多双语例句

百科

电气火灾报警系统

电气火灾报警系统又称漏电火灾报警系统,通过探测线路中的漏电流的大小来判断火灾发生的可能性,漏电是通过探测电气线路三相电流瞬时值的矢量和(用有效值表示)。探测器的传感器为零序电流互感器,零序电流互感器探测剩余电流的基本原理是基于基尔霍夫电流定律即流入电路中任一节点的复电流的代数和等于零,即ΣI=0。在测量时,三相线A、B、C与中性线N一起穿过零序电流互感器,通过检测三相的电流矢量和,即零序电流Io,Io=IA+IB+IC。在线路与电气设备正常的情况下(对零序电流保护假定不考虑不平衡电流,无接地故障,且不考虑线路、电器设备正常工作的泄漏电流),理论上各相电流的矢量和等于零,零序电流互感器二次侧绕组无电压信号输出。当发生绝缘下降或接地故障时的各相电流的矢量和不为零,故障电流使零序电流互感器的环形铁芯中产生磁通,二次侧绕组感应电压并输出电压信号,从而测出剩余电流。考虑电气线路的不平衡电流、线路和电气设备正常的泄漏电流,实际的电气线路都存在正常的剩余电流,只有检测到剩余电流达到报警值时才报警。